Last year I wrote about a code change proposal for the 2027 International Building Code (IBC) that was making its way through the ICC code development process.  The proposal, submitted by the ICC Committee on Health Care, would allow non-self-closing fire doors on unit entries for assisted living units as well as some other residential treatment facilities.  You can read the original post here.

When I wrote the post in 2024, I really didn’t think that the proposal would be approved.  Given the frequency of fires in residential buildings vs. the protection provided during a fire by a closed and latched fire door, it wouldn’t make sense to have those doors standing open.  Past fires in assisted living facilities and other apartment buildings have shown how an open fire door can compromise the means of egress and lead to fatalities.

Unfortunately, the proposal (FS65-24) has been approved, with a modification from the committee.  The following section will be included in the 2027 IBC, unless someone successfully intervenes:

716.2.6.1 Door closing. Fire doors shall be latching and self- or automatic-closing in accordance with this section.
Exceptions:
1. Fire doors located in common walls separating dwelling units or sleeping units in Group R-1 shall be permitted without automatic- or self-closing devices.
2. In Group I-1, Condition 2, fire doors located in corridors and serving sleeping units that do not include a cooktop or range shall be permitted without automatic- or self-closing devices.
3. The elevator car doors and the associated elevator hoistway doors at the floor level designated for recall in accordance with Section 3003.2 shall be permitted to remain open during Phase I emergency recall operation.
4. Fire doors required solely for compliance with ICC 500 shall not be required to be self-closing or automatic-closing.

The change in question is Exception 2, which applies to Group I-1, Condition 2 buildings.  Examples of Group I-1 facilities are alcohol and drug centers, assisted living facilities, congregate care facilities, group homes, halfway houses, residential board and care facilities, and social rehabilitation facilities.  Condition 2 applies to buildings where residents receiving custodial care are able to evacuate with limited verbal or physical assistance.

The modification limits the exception to dwelling units in these occupancies that do not have a cooktop or range – the doors to the units, typically 20-minute fire doors, will no longer be required to be self-closing or automatic-closing.  In my opinion, we will see the negative impacts of this change sooner rather than later.

Just two weeks ago a fire occurred in an assisted living facility in Massachusetts, resulting in 10 fatalities.  Initial investigations have shown that this fire was not caused by cooking equipment in the unit, but was likely related to smoking materials or an oxygen concentrator.  A closed and latched fire door on the unit of fire origin could have protected the corridor as a means of egress, instead of allowing it to fill with smoke and trap residents in their units.

The only positive thing I can say here is that codes are a minimum.  These doors can still be self-closing or automatic-closing, although the cost savings of omitting this hardware will likely be tempting.  We’ll have to wait and see how it all plays out, but I for one am really disappointed in this code change.

How about you?