Paul Timm of Allegion spends A LOT of time in schools, and when he sees a problem with a door opening, he sends a photo along. What do you think of this Wordless Wednesday exit?
Do you have photos to share? You can upload them on the Photo Submission page!
You need to login or register to bookmark/favorite this content.








This looks like it was constructed similar to a fire escape access, but without stairs on the outside. If it’s allowed for a fire escape then I don’t see a reason not to allow it on the ground floor, especially since this looks like an elementary school where kids could more easily fit under the low ceiling.
A few other issues that would be prohibited in new buildings:
– A handrail is only provided on one side of the inside stair.
– The handrail coincides with the top of the guard, but new handrails must be 34-38 inches in height whereas guards must be 42 inches in height.
– The mini door leads to the outside but does not have a tactile exit sign (i.e. “EXIT” in raised characters and Braille).
It would help to see the outside – is exterior grade high?
Sorry about you, tall teacher – you won’t fit.
Rarely do fools see the error of their misguided ways prior to a needless tragedy.
When I was a firefighter, we had a pair of old school buildings in our first-due that utilized these partial doors and exit stairs from a half story below grade. They exited at grade and did not allow for reentry (blank slab to the exterior). Given the location, it was a best case scenario and of course the buildings were sprinklered.
In this particular case, I don’t love the amount of potential fuel in, on and around the MOE.