Last week I posted some photos of very old Von Duprin panic hardware, and someone asked me about the open back strike shown in the post.  Open back strikes are not very common these days, so this topic makes a great “What’s that?” post!  I originally wrote about open back strikes in 2011, but I’ve here’s a new post for the next generation of iDigHardware readers…

An open back strike is used on a pair of doors, when one door has hardware that latches into the other door, AND the other door has hardware that can operate independently (not flush bolts).  For explanation purposes, I’ll call the door with the strike the inactive leaf, and the other door the active leaf, even though both doors are actually active.

The “active” leaf typically has mortise panic hardware, and the “inactive” leaf typically has vertical rod panic hardware.  The purpose of the open back strike is to allow both leaves to operate independently, without using a coordinator.  (If you’re not sure what a coordinator is, here’s a post on that topic.)

If the pair in the photo below had no open back strike and no coordinator, the inactive leaf could be opened with some difficulty because of the mortise panic hardware latch engaged in the strike.  It could then close in the wrong sequence and get hung up on the latchbolt of the mortise panic hardware.  This can also happen when a pair has an overlapping astragal with no coordinator – if the wrong leaf closes first, it sits against the astragal and doesn’t close properly.

The open back strike allows the door with the vertical rod panic to open and close without conflicting with the mortise panic hardware latchbolt.  The door with the mortise panic can also open and close without a conflict.  Open back strikes can be standard strikes or electric strikes.

Image: NFPA 80, Annex A

Here’s how NFPA 80 (2025) defines and addresses open back strikes for fire door assemblies:

3.3.125.2 Open Back Strike. A strike applied to the inactive leaf of a pair of doors and cut away at the back to allow either leaf to open or close independently.

6.4.4.11 Open back strikes shall be permitted to be used in lieu of conventional strikes only where specifically provided for in the published listings.

So where do you use an open back strike?  Only when all of the following conditions exist:

  • Pairs of doors (never on a single door)
  • The hardware on one leaf latches into the other leaf
  • Both leaves have hardware that allows them to be independently operated (not flush bolts)

The most common application is mortise panic (w/open back strike) x vertical rod panic.

You need to login or register to bookmark/favorite this content.