I’m sure the person who installed the louvers in the ice machine room doors in this hotel thought they were solving a problem (releasing the heat generated by the machine), but they created a new one. The doors are fire doors, and the louvers will allow smoke to pass through the openings rather than containing it to the rooms. Not to mention NFPA 80 doesn’t allow the installation of a louver as a job site preparation.
On a related note…did you know that although the IBC specifically prohibits louvers in certain locations, it does not currently address stairway fire doors? This will finally be rectified in the 2027 International Building Code (IBC) and International Fire Code (IFC). These codes will state: “Louvers are prohibited in fire door assemblies in interior exit stairways and ramps and exit passageways.”
On another related note…who can give me an example of an exit passageway???
Thank you to my retired AHJ friend who sent me today’s Wordless Wednesday photos!
You need to login or register to bookmark/favorite this content.
If they installed a brand new door, could they have installed a fire-rated louvre, like this by NGP:
https://www.ngp.com/product-detail/?productId=3626
Also louvres are not permitted in doors with lites
Interesting situation, in theory they could put in a new 45 min door with a listed louver but I don’t know if anyone with listing for a lite kit and a louver in the same door- even HM.
An exit passageway can lead building occupants to an entrance to an exit stair through an enclosed and protected passageway where the floor, walls, ceiling, and any openings within the exit passageway bear the same fire resistance rating as the stair shaft it leads to. Exit passageways are most commonly used in situations where the travel distance to reach the exit stair exceeds the limit allowed for that occupancy classification.
An exit passageway can also lead building occupants out of (away from) an exit stair when the exit stair does not discharge directly to the outside of a building. This is also commonly known as an exit discharge corridor. The floor, walls, ceiling, and any openings within the exit passageway also bears the same fire resistance rating as the stair it leads from. Exit discharge corridors are most commonly used when an exit stair does not discharge directly to the exterior of the building and the resulting unprotected travel distance, through the level of exit discharge, exceeds the limit allowed for that occupancy classification.
Is a rated door required for this application? Could it be one of those cases where its a “spare door” laying around the shop? Also, I recall a project where rated louvers were installed in rated doors due to stack effect, but the louvers had to be fire rated (usually a fuesable link) we hired a Warnock-Hersey certified contractor to the project. They did all the documentation and got approvals by the AHC.