This post was published inDoors & Hardware
With the continued focus on fire door assemblies, it’s important to be familiar with the basic requirements as well as what has changed in the more recent codes and standards. This article focuses on hinge requirements for fire doors, as mandated by NFPA 80 – Standard for Fire Doors and Other Opening Protectives.
Each edition of NFPA 80 refers to several ANSI/BHMA standards for hinges, including A156.1 (Butts & Hinges), A156.4 (Door Controls – contains pivot requirements), A156.17 (Self-Closing Hinges and Pivots), and A156.26 (Continuous Hinges). These standards contain detailed requirements about hinges, spring hinges, pivots, and continuous hinges. The edition of a referenced standard may vary from one edition of NFPA 80 to the next, so refer to the applicable edition of NFPA 80 to verify the effective date of the referenced standard.
Standard hinges are not typically required to bear a label indicating that they are listed for use on a fire door, but they must comply with the applicable referenced standard. Spring hinges must be labeled, as well as meeting the Grade 1 standards of A156.17. All hanging devices – hinges, spring hinges, continuous hinges, and pivots, must be provided as specified in the door and hardware manufacturer’s published listings or in accordance with NFPA 80. Various types of hinges are referenced in Annex A of NFPA 80, including 5-, 3-, and 2-knuckle hinges, full-mortise, half-mortise, full-surface, and half-surface hinges, and spring hinges, wide-throw, raised-barrel, and swing-clear designs.
A table within NFPA 80 includes a lot of important information about hinges for fire door assemblies. In recent editions of the standard, it is Table 6.4.3.1 – Builders Hardware: Hinges, Spring Hinges, and Pivots. The table specifies the minimum hinge size, type, and thickness, based on the door rating, width, and height. This table should be consulted to determine the correct hinge for each fire door assembly. For example, a steel hinge, mortise or surface-mounted, on a fire door that is 3 feet wide and 7 feet high must be at least 4 1/2 inches high and 0.134 inches thick. The maximum door size shown on this table for spring hinges is 3 feet wide and 7 feet high, so spring hinges installed on larger fire doors must be listed by the manufacturer for the appropriate door size.
Spring hinges are defined by NFPA 80 as, “A closing device in the form of a hinge with a built-in spring used to hang and close the door.” When spring hinges are installed on a fire door, NFPA 80 requires at least 2 spring hinges to be used, but does not specify which hinge locations the spring hinges must be installed in (top, center, or bottom hinge positions). Annex A suggests that spring hinges should be adjusted so that the door will latch properly when allowed to close freely from an open position of 30 degrees. This may be difficult to achieve long-term, and door closers are often used on fire doors because they provide greater control of the door and more reliable operation.
Fire door assemblies are required to have an adequate quantity of hinges as specified in the standard. A door up to 60 inches in height must have two hinges. Doors over 60 inches tall are required to have one additional hinge for each additional 30 inches of door height (or fraction thereof). For example, a 90-inch door would have 3 hinges, and a 100-inch door would have 4. Annex F – Door Hardware Locations, includes diagrams showing hinge locations for different types of swinging fire doors, but it’s acceptable for a manufacturer’s listings to allow hinges in alternate locations. NFPA 80 states that the distance between hinges may be greater than 30 inches.
NFPA 80 requires all hinges and pivots to be ball-bearing type, except for spring hinges, but other antifriction bearing surfaces are allowed if they meet the requirements of ANSI/BHMA A156.1 – Standard for Butts and Hinges. For hinges that are not of the ball bearing type, or are of lighter weight than what is allowed by Table 6.4.3.1, the hinges may be used if they are part of a listed assembly, and meet the test requirements of A156.1, and they have been tested to a minimum of 350,000 cycles. Pivot sets which are smaller or lighter weight than the minimums shown in Table 6.4.3.1 must meet the requirements of A156.4 – the standard for door controls (which also includes pivot requirements), and must be in accordance with the manufacturer’s label service procedures.
New requirements for pivots were added to NFPA 80 in the 2013 edition. The standard now mandates the quantity of pivots required for fire doors – a pivot set consisting of a top and bottom pivot and one intermediate pivot for doors up to 90 inches in height. For door heights greater than 90 inches, an additional intermediate pivot is required for each additional 30 inches of door height, or fraction thereof. NFPA 80 also allows the use of only intermediate pivots rather than a top and bottom pivot set. In some cases, this application is preferred for aesthetic reasons or because of the design of the frame. If only intermediate pivots are used, the quantities are the same as the requirements for hinges – two intermediate pivots for doors up to 60 inches in height, and an additional intermediate pivot for each additional 30 inches of door height or fraction thereof.
Requirements for continuous hinges were also added to NFPA 80 in the 2013 edition. Continuous hinges must be labeled and are required to comply with ANSI/BHMA A156.26, the standard for continuous hinges. The standard states that the length of continuous hinges must be within 1 inch of the height of the door leaves. Continuous hinges manufactured from steel, stainless steel, and aluminum are available for use on fire door assemblies, but only labeled continuous hinges may be used. When a continuous hinge is installed on a fire door assembly, labels that would be covered on the door and/or frame should be attached in an alternate location so they are visible for the life of the assembly. If a door or frame was prepped for standard hinges, and a continuous hinge is installed, the existing hinge preps need to be addressed in a manner that is acceptable per the manufacturer’s published listings.
One of the common problems regarding hinges on fire doors is related to the failure of the fastening method. Hinges are required to be secured as described in the manufacturer’s installation instructions and published listings. The standard specifies the type of fasteners that must be used – steel machine screws to secure mortise hinges to reinforcements in a door, and steel wood screws (No. 12 x 1 1/4 inch flat, threaded-to-the-head) for mortise hinges attached to wood and composite doors. Pilot holes must be drilled for these fasteners (5/32-inch in diameter). Steel through-bolts are required for surface-mounted hinges. For attachment to the frame, hinges must be secured with steel screws, but the type of screw will vary depending on the frame material.
In some cases, hinges must be shimmed during or after installation to properly align the door in the frame and bring clearances into compliance with NFPA 80. Shimming is allowed, but steel shims must be used. If correct clearances cannot be achieved by shimming the hinges, the NFPA 80 Handbook suggests adjusting compression anchors and/or repositioning sill anchors on slip-on drywall frames, or removing and reinstalling the frame. It’s much less disruptive to shim the hinges if possible, but shims of cardboard, wood, or other materials are not allowed for use on a fire door assembly.
The hanging components – hinges, pivots, and continuous hinges – are just one part of a fire door assembly, but they play an important role. If the hinges are specified, supplied, or installed incorrectly, the door will not swing freely. Incorrect fasteners may cause the door to sag or even come loose from the frame. Clearances can be affected by this misalignment, and the door may not close and latch properly, impacting the ability of the assembly to deter the spread of smoke and flames during a fire. The inspection requirements of NFPA 80 include verification that all components of a fire door assembly, including the hinges, “are secured, aligned, and in working order with no visible signs of damage;” Annex A indicates that hinges are one of the items that are especially subject to wear. For more information on fire door assemblies, refer to NFPA 80 – Standard for Fire Doors and Other Opening Protectives.
You need to login or register to bookmark/favorite this content.
Lori,
I vaguely remember that there was a time, perhaps fifteen to twenty years ago when NFPA 80 dictated a bearing rather than spring hinge in the upper location. Do you have any info on this?D5EV
Hi Bryan –
I researched that a few months ago for someone, and I didn’t find anything stipulating the locations for the spring hinges. I just looked in the 1999 edition and didn’t find a reference to the locations. It could have been in an older edition but it seems like an odd thing to remove.
– Lori
Hi Lori…SO the confusing question is always who is responsible for the listing on fire doors over 7′-0 high – the door manufacturer or the spring hinge manufacturer? Most of the spring hinge manufacturers say their hinge can be used on fire doors up to 8′-0, but is that enough or does the door manufacturer also have to be listed for their use? Your input is appreciated. Thanx–
Hi, Lori, we produce UL-Grade1 fire-rated self-closing hinge. And we hope to consult some fire door issue with you. can you replay me to have a discussion?
Hi Steven –
Let me know what questions you have and I will try to help.
– Lori
We have Aluminium series self-closing hinge. I want to know is any fire code can use this type of hinges. Also, I want to hire somebody like you who know SEO and have the door domain knowledge like you to help us write the introduction article. Can you do this or introduce someone to help me?
Lori,
Are weld on hinges allowed on hollow metal fire rated doors with internal metal stiffeners as long as the door is fire rated? For example the Southern Folger 205 Heavy Duty Hinge?
Hi Todd –
This is not specifically addressed by NFPA 80 so it would be up to the listings of the hinge, door, and frame manufacturers.
– Lori
Can a helper hinge be used in a fire rated opening?
Hi George –
If you mean a spring hinge, yes – they are allowed on fire doors although NFPA 80 includes some requirements/limitations on door size, quantity of spring hinges, etc.
– Lori
Stanley 225R 2C
Lori,
So in researching some of the more uncommon things I run into during Inspections, I saw this article in your archives. You mention that a 3070 fire door must have a minimum 4 1/2″ high hinge and be 0.134″ thick. In my research I found in the table (6.4.3.1) that you can have a 4″ high hinge with 0.105 thickness on the same 3070 fire door. Am I missing something here.
Paul
Hi Paul –
It looks like that line of the table in NFPA 80 applies to spring hinges. For standard hinges on a 3070 x 1 3/4″ door, I’m looking at the second line on the table which addresses doors up to 3080. Let me know if you disagree.
– Lori
[…] stated in the decoded NFPA 80 regulation, fire door assemblies must have an adequate number of hinges. A door with a […]
Hi. I live in a 55+ community with 5 mid-rise condominium buildings. 4 of the buildings unit doors have 2 spring hinges and 1 building unit doors have 1 spring hinge. I know that 2 spring hinges are NFPA 80 code for the 3680 fire door and we are upgrading all doors to meet code. Do you know when the code changed to have 2 spring hinges? The 1st building was built in 2000.
Thanks,
Tom
Hi Tom –
I don’t know exactly when the standard changed to require 2 spring hinges per door, but the question is…are these doors self-closing? Do the spring hinges close and latch the door? For a 3680 fire door, the listings of the spring hinges would have to specifically allow them to be used on a door of that size. I wouldn’t rely on spring hinges for that application.
– Lori
Can you use hinge fillers to fill butt hinge preps on a fire rated frame and then use a fire rated continuous hinge to hang the door?
Hi Tom –
Typically yes, but you should check with the frame manufacturer and also make sure to document the existence of the label if it will be covered by the hinge.
– Lori
Hello Lori,
First off, thank you for the abundance of reliable information you dig up for our industry.
It is truly appreciated.
I know this is an old post but….
Typically when a full-surface continuous hinge is used on a mineral core wood door it is because the wood door has failed.
This being said, even with using steel hinge fillers and a listed continuous hinge wouldn’t the door still be out of compliance since the door construction itself is compromised?
I typically always tell people it needs to be replaced.