I originally wrote this article nine years ago (how can that be???), but I’m receiving a lot of questions related to this topic.  Given the security concerns of schools and other facilities, it’s important to understand when the egress path is allowed to lead to an area enclosed by a fence and when the means of egress must continue through gates in the enclosure to reach the public way.  I have updated this article based on current code requirements.

This post was published in Doors & Hardware

School Fence aA few years ago, I worked as the hardware consultant on a data center project with extremely high security. On the interior door openings, there were many challenges and conflicts between the code requirements which mandated free egress and the need for security methods that included interlocks, delayed egress locks, and several levels of access control.

A security fence surrounded the building, with access control readers at the vehicular and pedestrian entrances to the site. In order to maintain this secure perimeter, the security consultant did not want to allow free egress through the gates that led to the public way. Because the paths from the building’s exterior doors to the public way are part of the means of egress (this portion is called the exit discharge), any gates encountered before reaching the public way would typically be required to comply with the egress code requirements. These include the mandates for one releasing motion to release the latch(es), no special knowledge or effort, no tight grasping/pinching/twisting of the wrist, and operable hardware mounted between 34 and 48 inches above the floor or ground.

Exterior gates are notoriously difficult to secure while providing free egress when required by the model codes. Locking/latching hardware may be defeated from the secure side of the gate, and many gate designs cannot easily accommodate the door closers needed to keep the gates closed and latched. Electrified hardware used on exterior gates can create additional challenges, due to exposure to the weather as well as unauthorized access to the release devices (like actuating the motion-sensor release for an electromagnetic lock from the secure side of the gate).

With today’s focus on security for schools, office buildings, and other types of facilities, it will likely become more common to see a building completely surrounded by a fence. Each opening in the fence that is equipped with hardware allowing free egress becomes a potential access point – for authorized or unauthorized individuals. While I am not recommending that we surround every building with a fence, or that there should be no gates to provide egress from the contained area, the International Building Code (IBC) does address this situation.

In recent editions of the IBC, this is covered in section 1028.5 – Access to a Public Way, which requires the exit discharge to provide direct and unobstructed access to a public way; typically the public way is a street or alley. The exception to this section states that when access to a public way can’t be provided, a safe dispersal area is required, where building occupants can wait for fire department assistance. This safe dispersal area – a location within the fenced area or enclosed court – must meet the following requirements:

  • The safe dispersal area must be large enough to provide at least 5 square feet of space for each building occupant (see below for variations on this requirement for stadiums and I-2 occupancies).
  • The area must be on the same lot and at least 50 feet away from the building, accessed by a safe and unobstructed path.
  • The area must be permanently maintained and identified as a safe dispersal area, and cannot be used for another purpose such as parking, storage, or temporary structures (these limitations on the use of the area are found in the IBC Commentary).

If these criteria are met, the fence surrounding the building would not be required to have gates that allow free egress, as the building occupants can gather safely in the enclosed area and wait for emergency responders to arrive.

For stadiums, the IBC (Section 1010.2.1 in the 2015 and 2018 editions, Section 1010.4.1 in the 2021 and 2024 editions) describes a safe dispersal area that provides at least 3 square feet per occupant, located a minimum of 50 feet from the enclosed area of the stadium.  If this safe dispersal area is provided, and if the stadium gates are under constant supervision when the stadium is occupied by the public, then panic hardware is not required to be installed on the stadium gates.

The IBC addresses secured yards for Group I-2 occupancies (hospitals, nursing homes, psychiatric hospitals, detox facilities, and foster care facilities) in a separate section of the code (407.9 in the 2015 IBC, 407.10 in the 2018, 2021, and 2024 editions). This section requires the safe dispersal area for I-2 occupancies to provide at least 30 net square feet for each bed and stretcher care recipient and 6 net square feet for ambulatory care recipients and other building occupants; as with other occupancy types, the safe dispersal area must be at least 50 feet away from the building. The use of a fenced area that is sufficiently sized for use as a safe dispersal area can be especially helpful for memory care units and behavioral health facilities, where a secured yard is often provided for the use of care recipients. In an emergency, this enclosure can provide a safe alternative to allowing care recipients to freely evacuate to a public way.

NFPA 101 – The Life Safety Code includes some language similar to the IBC, but only in relation to Detention and Correctional occupancies. In these facilities, sections 22.2.7 (new) and 23.2.7 (existing) allow exits to discharge into an enclosed court. Not more than two walls of the courtyard may be walls of the building, and the enclosed court must be large enough to provide a net area of 15 square feet per person at least 50 feet from the building.

The local codes and the Authority Having Jurisdiction (AHJ) should be consulted to verify the requirements for a specific jurisdiction. For sites where the requirements for a safe dispersal area cannot be met, gates which are properly sized, remotely located, and equipped with hardware that meets the egress requirements will likely be needed.

You need to login or register to bookmark/favorite this content.